Notification based on the workstation and on the operator acknowledgement level
This model is a combination of the two previous alarm management models:
The Alarm acknowledgment check box status (selected or not) indicated in Devices/Application/Alarms (for workstation priority) and System/Operator/Security (for operator priority) determines the resulting acknowledgement priority level for a given Operator-Workstation combination. For more information about the alarm acknowledgement check boxes, see Creating and modifying operator security levels and Defining Parameters.
| Workstation Alarm Acknowledgement | |||||
| Not selected | Selected | ||||
| Slider left | Slider right | ||||
| Operator Alarm Acknowledgement | Not selected | Never ackn. | Never ackn. | ||
| Selected | Slider left | Never first | Never first | ||
| Slider right | Never first | Product of both | |||
Resulting acknowledgement priority levels:
- Never ackn.: The operator and the workstation never receive any alarm acknowledgement notification.
- Never first: The operator and the workstation are never the first to receive any alarm acknowledgement notification.
- Always first: The operator and the workstation are always the first to receive any alarm acknowledgement notification.
- Product of both: The resulting priority level is calculated as a product of the operator priority level and the workstation priority level.
Enter the Acknowledge time-out delay. If the delay is exceeded, a new acknowledgement notification is sent.