Configuring an OSDP reader to a KT-1 controller
- On the EntraPass workstation, click the Devices tab, and click Controller.
- From the Controller list, select the controller that the reader is connected to.
- In the Controller window, click the KT-1 tab.
-
From the COM2 Protocol
list, select OSDP.
The RS-485 baud rate changes to 9600 and the Reader template changes to Default OSDP reader template. You can update these items.
-
To add readers, complete one of the following options:
- Use the following preferred option to manually add readers:
- Click the KT-1 tab.
- Click Add and, in the Address column, select or type the OSDP reader address. Accepted values range from 0 to 126.
- In the Door column, select the door to associate with the reader.
- Click Save.
- Use the following option to automatically add unassigned readers. This
feature only works for addresses 0 to 31 at the default baud rate of
9600:
- On the Controller window toolbar, click the Request unassigned modules icon.
- In the Request unassigned modules window, right-click the appropriate reader and select Assign module.
- Click Save.
- Use the following preferred option to manually add readers: