Defining an Input for a Group of Doors

This feature allows operators to setup an input that will allow unlocking a group of doors upon an input alarm. This feature can only be setup for groups of doors.

Note: If you only have one door that you want to setup to unlock upon an input alarm, create a group that will only include that door. To create groups, see Door Group Creation.

When the input being defined / edited is used for a door contact, a Door tab is displayed in the Input definition window.

  1. In the Input definition window, select the Doortab.
  2. Select the group of doors that will be unlocked upon input alarm.
  3. Select action to take once the doors are unlocked:
    • Latchwill keep the doors unlocked until an operator manually relocks them regardless of the input’s state.
    • Followwill keep the doors unlock until someone physically resets the inputs state. This option is the most appropriate for manual pull stations since they require special tools and/or user intervention to reset the alarm condition.
      • Example: For a door, part of a group, on a schedule; when the input is restored, it will lock the group of doors and return the door back to its original schedule.
    • Access will unlock the group of doors for the duration of the unlock time even if the input is back to its normal state.
      Note: This feature is not operational if communication links between the controllers and the Global Gateway are down.
Note: For more details about the Comment entry box, see Comment Field.