Configuring the KT-400 expansion modules
The KT-400 support expansion modules through its SPI expansion port. The SPI port is a 6-conductor cable bus to which several expansion modules are daisy-chained to add inputs, outputs, and relays.
Note: The KT-400 SPI port
maximum current draw is 500 mA, when the 12V AUX terminals are not used. External power
supply (12 VDC, 2 Amps) for the expansion module is required when the total current draw
exceeds 500mA on the SPI Port. For additional hardware details, refer to the KT-400
Ethernet Four-Door Controller Installation Guide, DN2003.
Thare are three expansion module types available:
- KT-MOD-INP16: The KT-MOD-INP16 is an input module that adds 240 zones to the KT-400 controller. Up to 15 input modules (16 input modules if used for elevator configuration) can be connected to a KT-400 for a total of 240 external inputs. Adding the 16 onboard inputs of the KT-400 gives a total of 256 inputs per KT-400. For further details, check the KT-MOD-INP16 KT-400 Expansion Module 16-Zone Input with SPI Cable, Install Sheet, DN1776.
- KT-MOD-OUT16: The KT-MOD-OUT16 is a 16-output module. It can be used for elevator access control with additional hardware. Up to 16 output modules can be connected to a KT-400 for a total of 256 outputs. For further details, check the KT-MOD-OUT16 KT-400 Expansion Module 16-Output with SPI Cable, Install Sheet, DN1781.
- KT-MOD-REL8: The KT-MOD-REL8 is an 8-relay outputs expansion module used as general relays or elevator control outputs. Up to 32 relay modules can be connected to a KT-400 for a total of 256 relays. For further details, check the KT-MOD-REL8 KT-400 Expansion Module 8-Relay Output with SPI Cable, Install Sheet, DN1786.
The following table summarizes the options associated with each module:
| Expansion Module | Options |
|---|---|
| KT-MOD-INP16 | Controller inputs (up to 256) and/or elevator inputs (up to 64 per elevator door) |
| KT-MOD-OUT16 | Outputs relays (up to 256) and/or elevator outputs (up to 64 per elevator door) |
| KT-MOD-REL8 (Note) | Relays (up to 256) and/or elevator outputs (up to 64 per elevator door) |
Note: There are already 4
relays available on the KT-400. To prevent redundancy unless it is planned, select the
Relay number assignments check box. The 9-16 relay
configuration is set by default.