-
From the Windows® Start menu: Start > All
Programs > EntraPass Global/Corporate/Special Edition > Workstation/Server > Express
Setup. You may also launch Express Setup by
clicking the Express Setup button from the registration window or gateway definition
window.
Note: The Operator login window appears only when
starting Express setup in stand-alone mode.
-
Enter your Operator user name and password, then click
OK. The OK button is enabled
when the Password field contains data.
-
Select the gateway for which you want to configure a connection, then click the
New connection button.
-
Enter the connection name in the connection description
field, then select the reader type.
-
Select the Controller type for this connection.
Note: The KTES option is available for a Multi-site Gateway
only.
There is no reader type or
number of controllers to select when the
controller type is a KTES.
-
Select the Reader type .
-
Set the Number of controllers .
-
Specify the Connection type . This indicates how the
connection communicates with the gateway
computer. The connection types available will follow the controller type
selection.
- Select Direct (RS-232 or USB) , if the connection
is integrated to the gateway computer and connected to it by an RS-232
serial port. If the connection type is direct, then you have to specify
the serial port (com:) as well as the controller connection baud rate
(usually set at either 9600 or 19200). The default value is 19200.
- Select Ethernet (polling) if the connection
communicates with the gateway through a terminal server device
(Lantronix) using a port number. Then you have to specify the terminal
server’s IP Address and Port number . To configure the terminal server,
follow the manufacturer’s instructions or refer to the terminal server
documentation.
- Select Dial-up (RS-232) modem if applicable.
- Select IP address (KT-400) if applicable.
Complete the associated tabs.
- Select IP address (KTES) if applicable. Complete
the associated tabs.
- Select IP address (IP Link) if applicable.
Complete the associated tabs.
-
Click OK .
-
Specify the minimum configuration for the controllers or KTES defined in the
site. This includes assigning a name to the controller/KTES, specifying the
passback option, and entering the serial number.
Note: The serial number column appears only
for the KT-100, KT-300, KT-400 controllers and the KTES. The
passback type column only appears for the KT-300
and the KT-400. The passback feature will not allow any card to re-enter
unless it has been used to exit. This requires that readers be used for both
entry and exit.
-
For a new site with a KTES, go to Step 14.
-
Check the Same
door
1 and 2 and Same
door 3 and 4 option if a reader is installed on each side of the
door. The Same door 3 and 4 boxes are available only when
you are using KT-400.
-
Select the appropriate Passback
type (none, soft or hard). If a door is defined as an access
door, there is no anti-passback defined for this door. An entry or an exit door
can be assigned a passback option.
-
Go to Step 16.
-
Check the Door contact
option.
-
Check the Postal lock option, if applicable, for a KTES
only.
-
Enter the Serial
number , if this column is displayed. The serial number
(S/N) is on a sticker and generally
starts with Axxxxxxx .
-
Click OK . The components associated with the controller
and to the site are created in the server database. By default, the KT-200 and
KT-300 are assigned two doors except for the KT-400 which is assigned four
doors, if the Same door option is not checked. The
following table summarizes default values that are assigned to
controllers.
Note: When the system is updating the database, the second status
flag turns red, indicating that the system database is locked. When you try
to access another system menu while the database is locked, an error message
appears. Simply wait until the system database becomes
available.
The following are default values assigned to controllers by the Express Setup
program.
Table 1. Express Setup controller default values
| Controller or KTES |
Door |
Relay |
Input zone |
Auxiliary output |
| KT-100 |
1 |
4 |
4 |
2 |
| KT-200 |
2 |
2 |
16 |
4 |
| KT-300 |
2 |
2 |
8 |
4 |
| KT-400 |
4 |
4 |
16 |
16 |
| KTES |
1 |
3 |
4 |
2 |
| KT-1 |
1 |
2 |
5 |
5 |
| KT-2 |
2 |
2 |
8 |
5 |
The following table summarizes how input zones are used by the system for
controllers.
Table 2. How the system uses input zones for controllers
| Input zone |
System use |
Controllers |
| 1 |
Door
1 contact |
KT-100, KT-200, KT-300, KT-400, KT-1,
and KT-2 |
| 2 |
Door
1 Rex |
| 3 |
Door
2 contact |
KT-300 |
| 4 |
Door
2 Rex |
| 5 |
Door
2 contact |
KT-400 and KT-2 |
| 6 |
Door
2 Rex |
| 9 |
Door
2 contact |
KT-200 |
| 10 |
Door
2 Rex |
| 9 |
Door
3 contact |
KT-400 |
| 10 |
Door
3 Rex |
| 13 |
Door
4 contact |
| 14 |
Door
4 Rex |
The following table summarizes how input zones are used by the
system for the KTES.
Table 3. How the system uses input zones for the KTES
| Input zone |
System use |
Kantech Telephone Entry System |
| 1 |
Door
Contact |
KTES |
| 2 |
Postal Lock |
| 3 |
Door
Rex |
| 4 |
Future |
The following table summarizes how output zones are used by the system.
Table 4. How the system uses output zones
| Auxiliary output |
Use |
Controllers |
| 1 |
LED (Door 1) |
KT-100, KT-200, KT-300 and KTES |
| 2 |
Buzzer (Door 1) |
| 3 |
LED (Door 2) |
KT-200 and KT-300 |
| 4 |
Buzzer (Door 2) |
| 1 |
OUT1 (Door 1) |
KT-400 |
| 2 |
OUT2 (Door 1) |
| 3 |
LED (Door 1) |
| 4 |
Buzzer (Door 1) |
| 5 |
OUT1 (Door 2) |
| 6 |
OUT2 (Door 2) |
| 7 |
LED (Door 2) |
| 8 |
Buzzer (Door 2) |
| 9 |
OUT1 (Door 3) |
| 10 |
OUT2 (Door 3) |
| 11 |
LED (Door 3) |
| 12 |
Buzzer (Door 3) |
| 13 |
OUT1 (Door 4) |
| 14 |
OUT2 (Door 4) |
| 15 |
LED (Door 4) |
| 16 |
Buzzer (Door 4) |
| 1 |
OUT1 (Door 1) |
KT-1 |
| 2 |
OUT2 (Door 1) |
| 3 |
LED (Door 1) |
| 4 |
Buzzer (Door 1) |
| 5 |
Unassignable |
| 1 |
LED (Door
1) |
KT-2 |
| 2 |
Buzzer
(Door 1) |
| 3 |
LED (Door
2) |
| 4 |
Buzzer
(Door 2) |
| 5 |
Unassignable |
Note: The remaining components (relays and input zones) are undefined, that
is, they have been created but not yet defined. Components that are defined are
grayed out. You cannot select them or change their description. You can change their
description in their respective definition menu (Devices > Relays/Input
zones).
By default, the system assumes that:
- The reader is ioProx Kantech XSF Format,
- The power supervision schedule is always valid,
- The failsoft delay is enabled for 45 seconds,
- The resistor type is none (KT-100, KT-300, KT-400 and
KTES),
- The wait for second card delay is 30 seconds.